        BS5308 Part1 Instrumentation Cable Polyethylene Insulated  | 
  
    | VDE Ref Code |  | 
  
    |  | 
  
    | PVC Sheath Version | LSOH Sheath Version: | 
  
    | RE-2Y(St)Y (Overall Screen) | RE-2Y(St)H (Overall Screen) | 
  
    | RE-2Y(St)Y PiMF(Individual Screen+Overall Screen) | RE-2Y(St)HPiMF(Individual Screen+Overall Screen) | 
  
    | RE-2Y(St)Y-SWA(Overall Screen+Steel Wire Armour) | RE-2Y(St)-SWA(Overall Screen+Steel Wire Armour) | 
  
    | RE-2Y(St)Y PiMF-SWA(Individual Screen+Overall Screen+Steel Wire Armour) | RE-2Y(St)HPiMF-SWA(Individual Screen+Overall Screen+ Steel Wire Armour | 
  
    | Construction |  | 
  
    | Construction: Annealed solid copper(Class 1),stranded(Class2), | Binder tape:A 23 micron p.e.t.p.tape applied with a | 
  
    | or fiexible(Class 5) to BS5360 . | minimum 50% overlap. | 
  
    | Insulation: Polyethylene to BS 6234 Type 03. | Collective screen: | 
  
    | Pair identification: | Aluminium/p.e.t.p.laminated tape applied with the metallic side | 
  
    | a)Collectively screened cables:Colour coded in | down in electrical contact with a 0.5mm 2 tinned copper | 
  
    | . | accordance with Colour Code Chart 1 on page3 | drain wire over the p.e.t.p.binder tape. | 
  
    | b)Individually screened pairs:One blue core and one | Outer protection: | 
  
    |  | black core in each pair.Pairs identified by numbered | Type 1 Extruded flame retardant PVC sheath. | 
  
    |  | screen isolation tape. | Type 2 Extruded polyethylene bedding,alvanised steel | 
  
    | Pair screens |  | wire armour,extruded flame retardant PVC sheath. | 
  
    | Aluminium/p.e.t.p.Laminated tape applied with the metallic | Minimum bending radius: | 
  
    | side down in electrical contact with a 0.5 mm 2 tinned copper drain wire. | Type 1 8 x diameter. | 
  
    | A 23 micron isolation tape is applied over the screening tape with a | Type 2 12xdiameter. | 
  
    | minimum 50% overlap. |  | 
  
    | Voltage rating | Temperature rating | 
  
    | 300 volt core to earth and 500 volt core to core at maximum | During Operation:-40 ℃+70℃ | 
  
    | temperature  of 65
 ℃ | During Operation:-0 ℃+50℃ | 
  
    | These cables are not for direct connection to the public mains supply |  | 
  
    |  |  | 
  
    | Electrical characteristics |  | 
  
    | 
      
        | Parameter |               Note |  |  |  
        | 0.5mm 2(1/0.8mm)
 | 0.5mm 2(16/0.2mm)
 | 0.75mm 2 (24/0.2mm)
 | 1.0mm 2(1/1.13mm)
 | 1.5mm 2(7/0.53mm)
 |  
        | Conductor resistance  |  | Ω/Km |  |  |  |  |  |  
        | Insulation resistance  |  |  |  |  |  |  |  |  
        | Mutual capacitance at 1 kH-One pair and two pair(Quad)cables with collective screen and all
 cables with individually screened pairs
 -Cables with only collective screen except one pair and two pair(Quad)
 |  |  |  |  |  |  |  |  
        | Capacitance unbalance at 1 kHz |  |  |  |  |  |  |  |  
        | Inductance/resistance ratio(L/R) |  |  |  |  |  |  |  |  
        | Test voltage
 | (Core:core)  | - |  |  |  |  |  |  |  
        | (Core:core) |  
        | Rated voltage  |  |  |  | 300/500 | 300/500 | 300/500 | 300/500 |  COLOUR CODE CHART 1 ORDERING OPTIONS  |